GE Digital Energy Power Quality SGT5000_100-150_UPS_GE01 Operating Manual Uninterruptible Power supply Digital Energy™ SG Series 100 – 120 –
Modifications reserved Page 10/82 OPM_SGS_USM_M10_M15_0US_V030.doc Operating Manual SG Series 100 – 120 - 150 kVA 2 INTRODUCTION An Uninterrupti
Modifications reserved Page 11/82 OPM_SGS_USM_M10_M15_0US_V030.doc Operating Manual SG Series 100 – 120 - 150 kVA 3 DESCRIPTION 3.1 BLOCK DIAGRAM
Modifications reserved Page 12/82 OPM_SGS_USM_M10_M15_0US_V030.doc Operating Manual SG Series 100 – 120 - 150 kVA 3.2 OPERATION MODES 3.2.1 Norma
Modifications reserved Page 13/82 OPM_SGS_USM_M10_M15_0US_V030.doc Operating Manual SG Series 100 – 120 - 150 kVA 3.2.3 Utility recovery operation
Modifications reserved Page 14/82 OPM_SGS_USM_M10_M15_0US_V030.doc Operating Manual SG Series 100 – 120 - 150 kVA 3.3 PARALLEL SYSTEM OPERATION 3.
Modifications reserved Page 15/82 OPM_SGS_USM_M10_M15_0US_V030.doc Operating Manual SG Series 100 – 120 - 150 kVA 3.3.2 Features of RPA parallel sy
Modifications reserved Page 16/82 OPM_SGS_USM_M10_M15_0US_V030.doc Operating Manual SG Series 100 – 120 - 150 kVA 3.4 RECTIFIERS PARALLELED ON THE
Modifications reserved Page 17/82 OPM_SGS_USM_M10_M15_0US_V030.doc Operating Manual SG Series 100 – 120 - 150 kVA 3.5 RECYCLING AT THE END OF SERVI
Modifications reserved Page 18/82 OPM_SGS_USM_M10_M15_0US_V030.doc Operating Manual SG Series 100 – 120 - 150 kVA 4 LAYOUT 4.1 LAYOUT SG Series 1
Modifications reserved Page 19/82 OPM_SGS_USM_M10_M15_0US_V030.doc Operating Manual SG Series 100 – 120 - 150 kVA 5 CONTROL PANEL 5.1 CONTROL PAN
Modifications reserved Page 2/82 OPM_SGS_USM_M10_M15_0US_V030.doc Operating Manual SG Series 100 – 120 - 150 kVA Model: SG Series 100 – 120 - 150 kV
Modifications reserved Page 20/82 OPM_SGS_USM_M10_M15_0US_V030.doc Operating Manual SG Series 100 – 120 - 150 kVA alarm General alarm condition It b
Modifications reserved Page 21/82 OPM_SGS_USM_M10_M15_0US_V030.doc Operating Manual SG Series 100 – 120 - 150 kVA 6 LCD SCREEN The user interfa
Modifications reserved Page 22/82 OPM_SGS_USM_M10_M15_0US_V030.doc Operating Manual SG Series 100 – 120 - 150 kVA 6.1 METERING MODE The metering m
Modifications reserved Page 23/82 OPM_SGS_USM_M10_M15_0US_V030.doc Operating Manual SG Series 100 – 120 - 150 kVA Rectifier Utility data screen This
Modifications reserved Page 24/82 OPM_SGS_USM_M10_M15_0US_V030.doc Operating Manual SG Series 100 – 120 - 150 kVA Load on phases screen 2 This scree
Modifications reserved Page 25/82 OPM_SGS_USM_M10_M15_0US_V030.doc Operating Manual SG Series 100 – 120 - 150 kVA 6.2 ALARMS The alarms mode is en
Modifications reserved Page 26/82 OPM_SGS_USM_M10_M15_0US_V030.doc Operating Manual SG Series 100 – 120 - 150 kVA 6.3 PARAMETERS The parameters mo
Modifications reserved Page 27/82 OPM_SGS_USM_M10_M15_0US_V030.doc Operating Manual SG Series 100 – 120 - 150 kVA 3 – Scroll to the next screen (+).
Modifications reserved Page 28/82 OPM_SGS_USM_M10_M15_0US_V030.doc Operating Manual SG Series 100 – 120 - 150 kVA 6.4 EDIT MODE The EDIT MODE is e
Modifications reserved Page 29/82 OPM_SGS_USM_M10_M15_0US_V030.doc Operating Manual SG Series 100 – 120 - 150 kVA 3 – Change the selected character
Modifications reserved Page 3/82 OPM_SGS_USM_M10_M15_0US_V030.doc Operating Manual SG Series 100 – 120 - 150 kVA Dear Customer, We thank you for s
Modifications reserved Page 30/82 OPM_SGS_USM_M10_M15_0US_V030.doc Operating Manual SG Series 100 – 120 - 150 kVA 3 – Change to 4800. metering 3 al
Modifications reserved Page 31/82 OPM_SGS_USM_M10_M15_0US_V030.doc Operating Manual SG Series 100 – 120 - 150 kVA 6.5 USER PARAMETERS Pressing the
Modifications reserved Page 32/82 OPM_SGS_USM_M10_M15_0US_V030.doc Operating Manual SG Series 100 – 120 - 150 kVA 3. Telephone numbers Tel1: Tel1
Modifications reserved Page 33/82 OPM_SGS_USM_M10_M15_0US_V030.doc Operating Manual SG Series 100 – 120 - 150 kVA 5. Printer Set-up The UPS is capa
Modifications reserved Page 34/82 OPM_SGS_USM_M10_M15_0US_V030.doc Operating Manual SG Series 100 – 120 - 150 kVA 6.6 EVENTS (ALARMS AND MESSAGES)
Modifications reserved Page 35/82 OPM_SGS_USM_M10_M15_0US_V030.doc Operating Manual SG Series 100 – 120 - 150 kVA Code Alarms Meaning 4115 LOW BAT
Modifications reserved Page 36/82 OPM_SGS_USM_M10_M15_0US_V030.doc Operating Manual SG Series 100 – 120 - 150 kVA Code Alarms Meaning 4405 K6 OPEN
Modifications reserved Page 37/82 OPM_SGS_USM_M10_M15_0US_V030.doc Operating Manual SG Series 100 – 120 - 150 kVA Code Alarms Meaning 4700 DC LOW
Modifications reserved Page 38/82 OPM_SGS_USM_M10_M15_0US_V030.doc Operating Manual SG Series 100 – 120 - 150 kVA 6.6.2 Messages list Code Messa
Modifications reserved Page 39/82 OPM_SGS_USM_M10_M15_0US_V030.doc Operating Manual SG Series 100 – 120 - 150 kVA Code Message Meaning 4561 TOTAL
Modifications reserved Page 4/82 OPM_SGS_USM_M10_M15_0US_V030.doc Operating Manual SG Series 100 – 120 - 150 kVA Preface Congratulations on your c
Modifications reserved Page 40/82 OPM_SGS_USM_M10_M15_0US_V030.doc Operating Manual SG Series 100 – 120 - 150 kVA 6.6.3 Event report SG Series In
Modifications reserved Page 41/82 OPM_SGS_USM_M10_M15_0US_V030.doc Operating Manual SG Series 100 – 120 - 150 kVA 7 OPERATION This symbol refers
Modifications reserved Page 42/82 OPM_SGS_USM_M10_M15_0US_V030.doc Operating Manual SG Series 100 – 120 - 150 kVA 7.1 PROCEDURES FOR SINGLE UPS 7.
Modifications reserved Page 43/82 OPM_SGS_USM_M10_M15_0US_V030.doc Operating Manual SG Series 100 – 120 - 150 kVA 7.1.2 Maintenance shutdown (Load
Modifications reserved Page 44/82 OPM_SGS_USM_M10_M15_0US_V030.doc Operating Manual SG Series 100 – 120 - 150 kVA 7.1.3 From Manual Bypass (Q2) to
Modifications reserved Page 45/82 OPM_SGS_USM_M10_M15_0US_V030.doc Operating Manual SG Series 100 – 120 - 150 kVA 7.1.4 Complete UPS shutdown (No L
Modifications reserved Page 46/82 OPM_SGS_USM_M10_M15_0US_V030.doc Operating Manual SG Series 100 – 120 - 150 kVA 7.1.5 Restore to normal operation
Modifications reserved Page 47/82 OPM_SGS_USM_M10_M15_0US_V030.doc Operating Manual SG Series 100 – 120 - 150 kVA 7.1.6 Restore to normal operation
Modifications reserved Page 48/82 OPM_SGS_USM_M10_M15_0US_V030.doc Operating Manual SG Series 100 – 120 - 150 kVA 7.2 PROCEDURES FOR UPS FUNCTIONIN
Modifications reserved Page 49/82 OPM_SGS_USM_M10_M15_0US_V030.doc Operating Manual SG Series 100 – 120 - 150 kVA 7.2.2 Complete UPS shutdown (No L
Modifications reserved Page 5/82 OPM_SGS_USM_M10_M15_0US_V030.doc Operating Manual SG Series 100 – 120 - 150 kVA Table of contents Page 1 IMPORT
Modifications reserved Page 50/82 OPM_SGS_USM_M10_M15_0US_V030.doc Operating Manual SG Series 100 – 120 - 150 kVA 7.2.3 Restore to normal operation
Modifications reserved Page 51/82 OPM_SGS_USM_M10_M15_0US_V030.doc Operating Manual SG Series 100 – 120 - 150 kVA 7.2.4 Restore to normal operation
Modifications reserved Page 52/82 OPM_SGS_USM_M10_M15_0US_V030.doc Operating Manual SG Series 100 – 120 - 150 kVA 7.3 PROCEDURES FOR PARALLEL SYST
Modifications reserved Page 53/82 OPM_SGS_USM_M10_M15_0US_V030.doc Operating Manual SG Series 100 – 120 - 150 kVA 4. Press “inverter on” ( I ) key o
Modifications reserved Page 54/82 OPM_SGS_USM_M10_M15_0US_V030.doc Operating Manual SG Series 100 – 120 - 150 kVA 7.3.2 Maintenance system shutdown
Modifications reserved Page 55/82 OPM_SGS_USM_M10_M15_0US_V030.doc Operating Manual SG Series 100 – 120 - 150 kVA 7.3.3 From Manual Bypass (Q2) to
Modifications reserved Page 56/82 OPM_SGS_USM_M10_M15_0US_V030.doc Operating Manual SG Series 100 – 120 - 150 kVA 4. Press “inverter on” ( I ) key o
Modifications reserved Page 57/82 OPM_SGS_USM_M10_M15_0US_V030.doc Operating Manual SG Series 100 – 120 - 150 kVA 7.3.4 Separate a Unit from the pa
Modifications reserved Page 58/82 OPM_SGS_USM_M10_M15_0US_V030.doc Operating Manual SG Series 100 – 120 - 150 kVA 7.3.5 Reconnect a Unit to a paral
Modifications reserved Page 59/82 OPM_SGS_USM_M10_M15_0US_V030.doc Operating Manual SG Series 100 – 120 - 150 kVA 7.3.6 Parallel system shutdown (N
Modifications reserved Page 6/82 OPM_SGS_USM_M10_M15_0US_V030.doc Operating Manual SG Series 100 – 120 - 150 kVA 7.2 PROCEDURES FOR UPS FUNCTIONING
Modifications reserved Page 60/82 OPM_SGS_USM_M10_M15_0US_V030.doc Operating Manual SG Series 100 – 120 - 150 kVA 3. Disconnect the Battery, in cas
Modifications reserved Page 61/82 OPM_SGS_USM_M10_M15_0US_V030.doc Operating Manual SG Series 100 – 120 - 150 kVA 7.3.7 Restore to normal operation
Modifications reserved Page 62/82 OPM_SGS_USM_M10_M15_0US_V030.doc Operating Manual SG Series 100 – 120 - 150 kVA 3 Press “inverter on” ( I ) key on
Modifications reserved Page 63/82 OPM_SGS_USM_M10_M15_0US_V030.doc Operating Manual SG Series 100 – 120 - 150 kVA 7.3.8 Restore to normal operation
Modifications reserved Page 64/82 OPM_SGS_USM_M10_M15_0US_V030.doc Operating Manual SG Series 100 – 120 - 150 kVA 3. Connect the Battery to all Uni
Modifications reserved Page 65/82 OPM_SGS_USM_M10_M15_0US_V030.doc Operating Manual SG Series 100 – 120 - 150 kVA 7.4 PROCEDURES FOR PARALLEL SYST
Modifications reserved Page 66/82 OPM_SGS_USM_M10_M15_0US_V030.doc Operating Manual SG Series 100 – 120 - 150 kVA 4. Press “inverter on” ( I ) key o
Modifications reserved Page 67/82 OPM_SGS_USM_M10_M15_0US_V030.doc Operating Manual SG Series 100 – 120 - 150 kVA 7.4.2 Maintenance system shutdown
Modifications reserved Page 68/82 OPM_SGS_USM_M10_M15_0US_V030.doc Operating Manual SG Series 100 – 120 - 150 kVA 7.4.3 From Manual Bypass (Q2) to
Modifications reserved Page 69/82 OPM_SGS_USM_M10_M15_0US_V030.doc Operating Manual SG Series 100 – 120 - 150 kVA 4. Press “inverter on” ( I ) key o
Modifications reserved Page 7/82 OPM_SGS_USM_M10_M15_0US_V030.doc Operating Manual SG Series 100 – 120 - 150 kVA 1 IMPORTANT SAFETY INSTRUCTIONS S
Modifications reserved Page 70/82 OPM_SGS_USM_M10_M15_0US_V030.doc Operating Manual SG Series 100 – 120 - 150 kVA 7.4.4 Separate a Unit from the pa
Modifications reserved Page 71/82 OPM_SGS_USM_M10_M15_0US_V030.doc Operating Manual SG Series 100 – 120 - 150 kVA 7.4.5 Reconnect a Unit to a paral
Modifications reserved Page 72/82 OPM_SGS_USM_M10_M15_0US_V030.doc Operating Manual SG Series 100 – 120 - 150 kVA 7.4.6 Parallel system shutdown (N
Modifications reserved Page 73/82 OPM_SGS_USM_M10_M15_0US_V030.doc Operating Manual SG Series 100 – 120 - 150 kVA 3. Disconnect the Battery from al
Modifications reserved Page 74/82 OPM_SGS_USM_M10_M15_0US_V030.doc Operating Manual SG Series 100 – 120 - 150 kVA 7.4.7 Restore to normal operation
Modifications reserved Page 75/82 OPM_SGS_USM_M10_M15_0US_V030.doc Operating Manual SG Series 100 – 120 - 150 kVA 3. Press “inverter on” ( I ) key o
Modifications reserved Page 76/82 OPM_SGS_USM_M10_M15_0US_V030.doc Operating Manual SG Series 100 – 120 - 150 kVA 7.4.8 Restore to normal operation
Modifications reserved Page 77/82 OPM_SGS_USM_M10_M15_0US_V030.doc Operating Manual SG Series 100 – 120 - 150 kVA 4. Press “inverter on” ( I ) key o
Modifications reserved Page 78/82 OPM_SGS_USM_M10_M15_0US_V030.doc Operating Manual SG Series 100 – 120 - 150 kVA 8 OPTIONS 8.1 COMMUNICATION OP
Modifications reserved Page 79/82 OPM_SGS_USM_M10_M15_0US_V030.doc Operating Manual SG Series 100 – 120 - 150 kVA 8.3 CONNECTION FOR OPTIONS WARNI
Modifications reserved Page 8/82 OPM_SGS_USM_M10_M15_0US_V030.doc Operating Manual SG Series 100 – 120 - 150 kVA Safety instructions when working wi
Modifications reserved Page 80/82 OPM_SGS_USM_M10_M15_0US_V030.doc Operating Manual SG Series 100 – 120 - 150 kVA 9 MAINTENANCE WARNING ! All mai
Modifications reserved Page 81/82 OPM_SGS_USM_M10_M15_0US_V030.doc Operating Manual SG Series 100 – 120 - 150 kVA 9.1.5 Long shut-down periods of t
Modifications reserved Page 82/82 OPM_SGS_USM_M10_M15_0US_V030.doc Operating Manual SG Series 100 – 120 - 150 kVA 10 NOTES 10.1 NOTES FORM It is
Modifications reserved Page 9/82 OPM_SGS_USM_M10_M15_0US_V030.doc Operating Manual SG Series 100 – 120 - 150 kVA Safety symbols and warnings Safet